MENU
banner 2018

PHYSICO-CHEMICAL TEST 2022

Date of Analysis: FEBRUARY 21, 2022

A. PHYSICAL TEST RESULT

PUMPING STATION      PHYSICAL ANALYSIS    METAL ANALYSIS REMARKS 
 Turbidity Color Arsenic Cadmium Lead
PNSDW LIMITS  5 NTU  10 ACU 0.05 mg/L 0.003 mg/L 0.01 mg/L
1. Poblacion Pumping Station  0.35  3 <0.005 <0.001 <0.005 Passed
2. Sto. Tomas Pumping Station 0.20  3 <0.005 <0.001 <0.005 Passed
3. San Josef Pumping Station 0.20  3 <0.005 <0.001 <0.005 Passed
4. Sinasajan Pumping Station 0.30  3 <0.005 <0.001 <0.005 Passed
5. Poblacion IV Pumping Station 0.35  3 <0.005 <0.001 <0.005 Passed
6. Sinasajan Pumping Station 2 0.35  3 <0.005 <0.001 <0.005 Passed

B. CHEMICAL TEST RESULT

PUMPING STATION   CHEMICAL ANALYSIS    REMARKS 
pH Total Dissolved Solids Nitrate
 PNSDW LIMITS 6.5 - 8.5  500 50
1. Poblacion Pumping Station 8.4 199 0.1 Passed
2. Sto. Tomas Pumping Station 8.1 221 0.2 Passed
3. San Josef Pumping Station 8.7 196 <0.006 Passed
4. Sinasajan Pumping Station 8.3  203 0.01 Passed
5. Poblacion IV Pumping Station 8.5 197  <0.006 Passed
6. Sinasajan Pumping Station 2 8.3 214  <0.006 Passed

C. MICROBIOLOGICAL TEST RESULT

PUMPING STATION   CHEMICAL ANALYSIS (SOURCE& CONSUMERS' TAPS) REMARKS 
 Escherichia Coli Total Coliforms Fecal Coliforms
 PNSDW LIMITS Negative  <1.1 MNP/100mL <1.1MNP/100mL
1. Poblacion 1 Pumping Station Negative <1.1 <1.1 Passed
2. Sto. Tomas Pumping Station Negative <1.1 <1.1 Passed
3. San Josef Pumping Station Negative <1.1 <1.1 Passed
4. Sinasajan Pumping Station Negative <1.1 <1.1 Passed
5. Poblacion IV Pumping Station Negative <1.1 <1.1 Passed
5. Sinasajan Pumping Station 2 Negative <1.1 <1.1  Passed
 
 
NOTE:
PNSDW    :   Philippine National Standards for Drinking Water
NTU         :   Nephelometric Turbidity Unit / a unit measuring the lack of clarity of water
ACU          :   Apparent Colour Unit
 MNP        :  Most Probable Number